In an RS-485 daisy chain connection it is crucial that the resistors are properly installed and the cable is an AWG 24 Twisted pair


image




RS-485
RS-485 signaling relies upon balanced and differential signaling scheme and has many advantages over unbalanced signaling such as RS-232, such as strong noise immunity and multi-drop configuration capability. These are the most frequently asked questions on using RS-485 signaling systems, which are worth reading before designing an RS-485 BioStar network system.


Cable


The RS-485 transmission system requires twisted-pair cables for best results, to maximize its noise rejection characteristics. The characteristic impedance of the cable is recommended to be 120 ohms. 


Please Do Not Use Ethernet cable but only below recommended cable

 

CableSizePairsImpedance
Belden 984124 AWG Str (0.20 mm²)1120 Ohms
Belden 984224 AWG Str (0.20 mm²)2120 Ohms
Belden 8284124 AWG Str (0.20 mm²)1120 Ohms
Belden 8284224 AWG Str (0.20 mm²)2120 Ohms
Belden 8984124 AWG Str (0.20 mm²)1120 Ohms
Belden 8984224 AWG Str (0.20 mm²)2120 Ohms
Alpha Wire 641224 AWG Str (0.20 mm²)1120 Ohms
Alpha Wire 641324 AWG Str (0.20 mm²)2120 Ohms
General Cable C0841A24 AWG Str (0.20 mm²)1120 Ohms
General Cable C0842A24 AWG Str (0.20 mm²)2120 Ohms
Connect-Air W241P2050FRIB24 AWG Str (0.20 mm²)1120 Ohms
CAE Groupe
B9842NHT500
24 AWG Str (0.20 mm²)
2120 Ohms


Termination


As the cable gets longer, it acts as a transmission line, and the signals tend to reflect at the end of the line. To suppress this reflection, it is recommended to add termination resistors between signal pairs at both ends of the cable. The BioStar devices have on board termination resistors that can be enabled through slide switches or software configuration, so you may enable it if a device is placed at one of the ends of the cable.

  • Use proper resistor for termination. The resistance should match the characteristic impedance of the cable. As the RS-485 system recommends 120 ohm cables, the BioStar devices have 120 ohm resistors on board.

  • Place at the right place. The resistors should be placed at both ends of the cable to suppress line reflection. DO NOT PLACE more than two termination resistors within a cable.


For BioStar 2 refer to the below article as well:

RS485 Mode (Master, Default, Slave)



Maximum Slave Devices


One master device can connect up to 31 slave devices, but up to 8 fingerprint devices are able to be connectable through RS485. 

We recommend a minimum number of RS485 connected fingerprint devices considering the number of users and connected devices.
This is because it can lead to slow matching speed depending on the device which is used for the master device. 


However, CoreStation has a different specification. Corestation supports 5 RS-485 ports and up to 31 devices can be supported per port and a maximum of 64 slave devices can be supported by CoreStation in total.

Sample CoreStation Configuration 1
Port 1: 31 slave devices
Port 2: 31 slave devices
Port 3: 2 slave devices 


Sample CoreStation Configuration 1

Port 1: 10 slave devices 

Port 2: 10 slave devices 

Port 3: 10 slave devices 

Port 4: 10 slave devices  

Port 5: 24 slave devices 


Daisy Chain

 

Avoid using long stubs for each node. Long stubs act as transmission lines and should be kept as short as possible if unavoidable.

 

Do not use star-shaped wiring. This makes the transmission line system complicated and hard to suppress line reflections if not impossible.

 




CoreStation Sample Configuration:
- Install the termination resistor on each ends of the daisy chain (red box)

- CoreStation has a internal termination resistor so turn the DIP switches on 

[Device Manual]



Ground
A common misunderstanding in RS-485 network that it only requires two-wire cables is wrong, and it requires a ground wire to equalize node voltage differences. Ground potential differences are harmful in signal quality and signal transceiver’s reliability, so it should be kept as low as possible within a network. A simple approach is to use ground wire at the cost of ground loop current.