We would like to guide you on how we can replace the site where 3rd party controller and RFID readers are installed by Wiegand cable with Suprema CS-40 controller, BER2, and/or XPD2.
1. Check Wiegand cable
1.1 Wiegand cable should be Shielded twisted 2 pair cable. In order to connect RS485+, RS485- and GND to the Wiegand cable, the cable should be 2 pair cable or more.
1.2 If the cable length is not long enough to connect BER2 or XPD2 with CS-40, you can add cable as below. Note that the cable should be shielded twisted pair cable.
** Sample cable
- AWG 24 Belden 9504 Shielded Twisted Pair Cable
- AWG 24 Alpha 5472C Shielded Twisted Pair Cable
2. Install terminating resistance
2.1 In case the Wiegand cable characteristic impedance is 120ohm, switch ON terminating resistance of CS-40 and install 120ohm terminating resistance to the reader.
** Please check cable characteristic impedance with the cable company
2.2 In case that the Wiegand cable characteristic impedance is not 120ohm, switch OFF terminating resistance of CS-40. It is required to install terminating resistance to both CS-40 and reader.
3. The max. quantity of BER2 or XPD2 that can connect to CS-40
3.1
- (1:1) 5ea readers can connect to CS-40
- (1:2) 10ea readers can connect to CS-40
Ex e-2.
** Please note that terminating resistance must be installed to the reader and switch off the terminating resistance of CS-40 for daisy chain configuration.