Author: Krista Kim, Sales Manager I Suprema Europe 


1. CS-40 Network Reset and Factory Default


Q1: How to reset the CS-40 network? 

     A: Push the init button on CS-40 more than 3 seconds.  

* For more details,  please refer to the link below.

[Both BioStar] Network and Factory Default W2, P2, CS-40


Q2: How to do the factory default setting of CS-40?

     A-1: Factory default setting by BioStar2

           > Connect CS-40 with BioStar2

           > Go to  BioStar 2 →Settings → Security → Advanced Security Settings
                → Secure Communication with the Device.             This MUST BE SET TO USE ’ and click ‘Apply’.

           > Wait until CS-40 connects to the Server 

           > Push the init button on CS-40 4 times straight 

     A-2: Factory default setting by CS-40 SETUP Manager

          > Connect CS-40 with PC

           > Access web browser at https://169.254.0.1:3001 

           > Log in CS-40 SETUP Manager 

           > Click the ‘Factory Default’ button on configuration page 


* For more details,  please refer to the link below.

[CS-40] How to configure CS-40 IP configuration via SETUP Manager


2. CS-40 Network Setting  

Q1: How to set CS-40 IP? 

     A-1: Connect CS-40 with PC in 1:1 and access the web browser at https://169.254.0.1:3001  

           and log in CS-40 SETUP Manager. You can configure CS-40 IP. 

     A-2: Connect CS-40 with BioStar2 and configure CS-40 IP in the Device setting.  

 * For more details,  please refer to the link below.

Suprema CS-40 SETUP Manager

[BioStar 2] CS-40 Setup Manager Release


3. The number of doors controlled by CS-40

Q1: How many doors does a CS-40 support? 

     A: CS-40 has built-in 4 relays, which are to control 4 doors. By adding slave device via RS485, it    

       can control up to 52 doors, and via Wiegand, control up to 132 doors. 

 

Q2: How many RS485(OSDP) devices can be connected to CS-40?

     A: 64ch. Each port supports up to 31 slave devices with a daisy chain. 

 

Q3: How many Wiegand devices can be connected to CS-40?

     A: 132ch. CS-40 has 4 Wiegand ports, and 64ea DM-20, which has 2 Wiegand ports, can connect to 

        CS-40 by RS485. 

 

Q4: How many doors can DM-20 support? 

     A: DM-20 has 4 relays which support 4 doors with RS485 devices. 

* For more details,  please refer to the link below

[BioStar 2] Maximum Slave Devices with CS-40

[BioStar 2] CS-40 2 Sample Door Configuration


4. How to use 3rd party reader with CS-40  

Q1: Can we use 3rd party card reader with CS-40? 

     A: Yes, All standard card readers that support Wiegand output can work with CS-40.

 

Q2: Can we use 3rd party keypad reader with CS-40? 

     A: No, CS-40 doesn’t support the single key output from Wiegand signal, so it cannot use with 3rd 

        party keypad reader.  

 

Q3: Can we use 3rd party fingerprint reader with CS-40? 

     A: Yes, 3rd party fingerprint reader can connect with CS-40 by Wiegand. CS-40 has a matcher

       that supports Suprema template. You can either use Suprema fingerprint slave reader BER2 or Suprema

         intelligent fingerprint reader by RS485(OSDP) connection.

* For more details,  please refer to the link below.

[BioStar 2] OSDP Protocol Support


5. How to use XPD2 or BER2 with 3rd party controller  

Q1: Can we use XPD2 with 3rd party controller?  

     A: Yes, XPD2 can connect with 3rd party controller by Wiegand or RS485. You can easily configure XPD2 

        setting via Suprema Device Manager Application via mobile phone. 

 

Q2: Can we use BER2 with 3rd party controller?  

     A: Yes, If the 3rd party controller can store the fingerprint template, BER2 can be used with the ACU. 

* For more details,  please refer to the link below.

[BioStar 2] Suprema Device Manager Mobile App New Features and Configuration Guide

[BioStar 2] OSDP Protocol Support


6. How to replace a 3rd party controller and Wiegand reader with CS-40, XPD2 and/or BER2

Q1: Can we connect Wiegand cable with RS485 cable of XPD2 and BER2? 

     A: Yes, Check Wiegand cable at the site is shielded twisted 2 pair cable. If it is, you can connect 

        Wiegand 3 core cable with RS485 cable (TRX+,TRX-,GND) of XPD2 and/or BER2.

 

Q2: How many can XPD2 and BER2 connect with CS-40 when being cabled by RS485  

      and Wiegand cable together?

     A: Max.10ea. 

* For more details,  please refer to the link below.

 [CS-40] How to replace a 3rd party controller and Wiegand RFID readers with Suprema CS-40 controller, BER2 and/or XPD2 


7. Suprema platform compatibility with CS-40

 

Q1: Which Suprema device can be used with CS-40? 

     A: 1) Slave RFID reader: XPD2

         2) Slave Biometric reader: BER2

         3) All intelligent biometric readers

         4) All peripherals 

 

Q2: Does XPD2 (Rev 2) support Airfob Pass? 

     A: Yes, XPD2 (Rev 2) supports Airfob Pass(Suprema Mobile Access) 

* For more details,  please refer to the link below.

[BioStar 2] Upgraded Hardware Introduction : XPass D2 (Rev 2)


8. Maximum Biometric Devices with CS-40  

Q1: How many fingerprint readers can connect with CS-40? 

     A: We recommend having less than 8 fingerprint devices as slave devices for performance reasons. 

 * For more details,  please refer to the link below.

[BioStar 2] Maximum Slave Devices with CS-40


Q2: How many face authentication readers can connect with CS-40? 

     A: 5ch. Face reader can connect to each RS-485 port of CS-40 one by one. 

* For more details,  please refer to the link below.

[BioStar 2] Maximum Slave Devices with CS-40


9. Integration

Q1: Which VMS system can be used with CS-40? 

     A: Milestone. Suprema BioStar2 software is integrated with Milestone Xprotect. You can monitor video   

        and control from a single interface. 

* For more details,  please refer to the link below.

[BioStar 2] Milestone VMS Integration


Q2: How can we integrate CS-40with 3rd party software? 

     A: You can use BioStar2 Device SDK. Please download it from the link.    

* For more details,  please refer to the link below.

BioStar 2 Device SDK manual

BioStar 2 Device SDK Download Link


10. Power

Q1: What is the specification of Power AUX IN of CS-40? 

     A: 12V DC, 3A

 

Q2: What is the power output of CS-40? 

     A: 12V/1.5A. Slave device or Wiegand device or lock etc., can be powered within 1.5A. In case of 

        exceeding 1.5A, you need a separate power supply. 


11. Installation  

Q1: How to connect slave device with CS-40 by RS485? 

     A: Use an AWG24 twisted pair with a maximum length of 1.2km for RS485 cable which has 120 ohm 

        impedance. It is mandatory to wire in parallel format.  

* For more details,  please refer to the link below.

[Both BioStar] Daisy Chain and RS485 Connection


12. Configuration  

Q1: Can we use PIN Only Mode with Xpass D2 Keypad reader?  

     A: Yes, You can create virtual card number in User Configuration in BioStar2 and enable XPD2  

        authentication mode to “Input card ID from keypad” available.   

 

Q2: Can we configure supervised input? 

     A: Yes, CS-40  input No.0~7. can be used for normal TTL    input or supervised input. 

 [BioStar 2] Supervised Input 


Q3: Can we use fire alarm panel with CorStation ? 

     A: Yes, you can connect CS-40 input with fire alarm panel. BioStar2 Standard license is required.

* For more details,  please refer to the link below.

[BioStar 2] Using Card Only or PIN Only Mode with XPass D2

[BioStar 2] CS-40 2 Sample Door Configuration

How to configure Fire Alarm Zone?


13. Offline function  

Q1: When the host computer goes offline, can CS-40 work? 

     A: Yes, It works in local zone mode. CS-40 has a capacity of storing 5,000,000 logs. When the 

        network is back, it will upload all the logs to the host. However, it is not supported in global zone mode.  

 

Q2: When slave device is cut from CS-40, can the slave work? 

     A: No, it’s not supported. 

 

Q3: Can we connect CS-40 to another CS-40 by RS485 for back-up? 

     A: No, it’s not supported. 


14. Replacement function  

Q1: When CS-40 is failed and should be replaced, do we have to reconfigure settings?

     A: Yes, Currently, you should reconfigure all the settings.