Could we connect Suprema device to Access Control Unit through Wiegand?
Could we use Wiegand of Suprema device to connect Access Control Unit?
[Figure 1. System Configuration for Wiegand Output ]
Yes, Suprema device can be a reader to send Wiegand signal to 3rd party Access Control Unit such as NET2 of PAXTON , iSTAR of CCURE, or OnGuard Controller of Lenel.
You should consider the below step to use Wiegand data between Suprema Device and 3rd party ACU.
[Figure 2. Step for Wiegand Output Usage]
To send WIEGAND output, you should check the below configuration and follow the description.
Please make sure that if the user information is stored in the 3rd party ACU's software.
Step 1. Wiegand Wiring
1. Refer Wiegand cable from device manual and connect 3 cables of Wiegand part between Suprema device and ACU
- Most important part is that pin map of Wiegand port of a device.
[Figure 3. BioStation A2 - Device port for each function]
[Figure 4. BioEntry W2 - Wiegand Cable]
Step 2. Device Configuration
1. Add a device to BioStar 2
2. Confirm your card type which you are going to use
2-1. CSN Card type: Mifare (13.56 Mhz), Felica (13.56Mhz), EM Card (125 kHz)
2-2. WIEGAND card Type: iClass Card (13.56Mhz), HID Prox Card (125 kHz)
3. Follow the configuration following the card type
<CSN CARD>
3-1. Click [Setting] > [Card Format]
following3-2. Click the red box as follows to add new Wiegand format in accordance with Wiegand data
3-3. Let's say you have 34 bit Mifare CSN card. The configuration is as follows.
3-3 Click [Device] and choose the connected device to configure additional configuration
3-4 Click CSN Card Format and select Format Type as [Wiegand]
3-5 Choose one of Wiegand format from the [Wiegand Format] of CSN Card Format
<Wiegand Card>
3-6 Choose the predefined card format from the [Wiegand Card Format]
3-7. If there is not a Wiegand format that you need, go to [Setting]>[Wiegand] and configure it
4. Click [Advance] and set WIEGAND INPUT/OUTPUT to [OUTPUT]
5. Set Pulse Interval from 10000 to 5000 or correct information referring to the below list.
<ACU and Wiegand Pulse List>
AMAG - Symmetry:
Pulse width: 40
Pulse Interval: 2000
Brivo - ACS6000:
Pulse width: 40
Pulse Interval: 1000
iStar - CCure - Software House:
Pulse width: 40
Pulse Interval: 1000 (iStar Ultra G2/Edge)
Pulse Interval: 5000 (iStar Ultra)
NOTE: for devices such as FaceStation F2, BioStation 3, X-Station 2:
- Tested with Panels: iStar Ultra, Ultra G2, Edge
- Panels iPro are discontinued, hence information about such is deprecated
CDVI:
Pulse width: 40
Pulse Interval: 800
DMP:
Pulse width: 40
Pulse Interval: 10000
Genetec:
Pulse width: 40
Pulse Interval: 10000
Pulse width: 20
Pulse Interval: 2000
Hartman Controls - PRS:
Pulse width: 40
Pulse Interval: 1000
Honeywell:
Pulse width: 40
Pulse Interval: 800
IMron:
Pulse width: 50
Pulse Interval: 2000
Keyscan:
Pulse width: 40
Pulse Interval: 5000
Lenel:
Pulse width: 40
Pulse Interval: 5000
NAPCO: Continental:
Pulse width: 40
Pulse Interval: 700
Paxton - Net2:
Pulse width: 40
Pulse Interval: 800 - 2000 or for some devices 10000
PCSC :
Pulse width: 40
Pulse Interval: 5000
(Need also sometimes Facility Code set to 255)
Rosslare:
Pulse width: 40
Pulse Interval: 10000
SALTO
Pulse width: 40
Pulse Interval: 10000
(Need also Fail code to be set to 0xFF)
True Portal
Pulse width: 50
Pulse Interval: 2000
Security Expert (Schneider)
SP-C Controller
Pulse width: 20
Pulse Interval: 200
- Or, you can adjust the parameter after referring the configuration setting of software of your 3rd party ACU.
Step 3. User Configuration
a 1. Go to [User] and add new user
2. Click [Card]
3. Choose the card type and card data format
4. Click [Read Card] and place your card
a 4-1. If you do not have physical card, you can register user ID instead of card ID. Refer the link below.
[BioStar 2] Sending Out User ID Through Wiegand
4-2. If you would like to enroll a finger or face, you can register for the user information.
[BioStar 2] How to enroll a user
5. Click [Apply] to store the user information
Step 4. Test
1. Scan registered fingerprint or card.
2. If user authentication succeeds, the Wiegand signal will be sent from Suprema device to ACU.
Relevant articles
[BioStar 2] Troubleshooting Wiegand output issues
[BioStar 2] Sending Out User ID Through Wiegand